4 Installing the VLinx Serial Server
The preferred PC to I/O module communication option requires a VLinx serial server. This section will
guide you through installing the Ethernet to RS485 serial server.
Mounting the VLinx serial server
Mount the VLinx serial server into the same enclosed panel as the I/O module in one of the following
ways:
using a DIN rail (preferred for quick change-outs)
using four screws and the mounting holes provided on the cover plate
Be sure to leave space on either side for wiring.
Connecting power to the VLinx serial server
To connect power to the VLinx serial server:
1. Set the DIP switches on the VLinx serial server to the OFF position.
2. Connect the power cable to the DC-IN jack on the top of the VLinx serial server.
3. Plug in the wall-plug power supply.
4. If the Power LED is not lit, make sure that 12VDC is present at the power input terminal.
Connecting the VLinx serial server to the network
To connect power to the VLinx serial server:
1. Connect one end of a standard Ethernet network cable to the VLinx serial server.
2. Connect the other end of the network cable to the router.
Configuring the VLinx serial server
To configure the VLinx serial server (match the settings illustrated in the figure below, i.e., Server
Properties):
1. Download the VLinx documentation from http://www.bb-elec.com/product_family.asp?familyid=2
.
2. Using the VLinx documentation and the VLINX software, set the VLinx serial server address to a
unique network address. Typically this should be 192.168.1.91 but could vary based on the IP
ranges used by the installed router.
3. Set the VLinx serial server port number to 4000.
Note: You can use any port number as long as you specify the correct port number when you
configure the ENV climate control system software.
4. Set the serial communication parameters to 9600 baud, 8 data bits, and no parity.
5. Open the VLINX by removing the two screws on the side. You will see two jumpers on pin 78.
Move them to the location shown below so that they are placed across the two pins in each of the
two locations.
Installation Guide Page 9 of 20 Copyright 2009