5 Installing Thermostats Include a communicating thermostat as part of the system when managing a typical forced air heating and cooling system. You

Página 4 - 1 About this Guide

6 Communication Wiring After you install the various components of the ENV climate control system, you must set up the communication wiring so the c

Página 5 - 2 Overview of the System

7 Wiring Equipment to the I/O Module Use a maximum wire size of 18AWG for wiring inputs and outputs. A 22AWG wire is the recommended size for inputs.

Página 6 - • a router

3. Connect digital input wiring as follows: 4. If the input is DC volts or milliamps, remove the module cover and set the configuration jumper for

Página 7 - Mounting the I/O module

3. To use the Ai8_R13 to drive high voltage loads (120VAC or greater), use an external load relay to separate the high voltage from the I/O module.

Página 8

The AiO8 only provides a 0-10 volt DC output: The AiO8 always requires an external 12VDC relay to switch any load as it only outputs a 0-10 volt s

Página 9

When using an external 12 volt DC relay, the energize voltage must be10 volts or less. The coil impedance must be greater than 500 ohms. An RIBTU1C (

Página 10

Wiring analog outputs You can wire analog outputs to the AiO8 DataNab module. Use analog outputs to control proportional type devices such as a valve

Página 11 - 5 Installing Thermostats

8 Supported Sensors and Control Devices This section identifies the various sensors and control devices you can use with Climate Automation Systems’

Página 12 - 6 Communication Wiring

© 2008 Climate Automation Systems. All Rights Reserved. No part of this document may be photocopied, reproduced, stored in a retrieval system, or tra

Página 13

Installation Guide Page 20 of 20 Copyright 2008 Thermocouple probe High pressure sensors for mounted NPT security TC-NPT http://www.omega.com/ppt/

Página 14 - Wiring digital outputs

Table of Contents 1 About this Guide ...

Página 15

1 About this Guide This guide provides the instructions for installing and configuring Climate Automation Systems’ ENV climate control system. Audi

Página 16

2 Overview of the System ENV is an energy management system that controls, manages, and monitors all aspect of a building’s environment. ENV is the

Página 17

Prerequisites to installation Before you begin installation of the ENV climate control system, ensure the following are available: • an active exte

Página 18 - Wiring analog outputs

3 Installing the Input/Output Module The ENV climate control system uses one or more input/output modules to interface with the climate control devic

Página 19

To connect power: 1. Make sure that the power source is off. 2. Connect the power wires to the module’s lower power terminals labeled 24VAC and . I

Página 20

4 Installing the VLinx Serial Server The preferred PC to I/O module communication option requires a VLinx serial server. This section will guide you