Residential Control Systems TR16 Guia de Instalação Página 17

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 20
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 16
When using an external 12 volt DC relay, the energize voltage must be10 volts or less. The coil
impedance must be greater than 500 ohms.
An RIBTU1C (single pole double throw) or RIBTU2C (double pole double throw) relay is an ideal
external relay for use with the AiO8 I/O module as it can handle loads of 10 amps resistive or 1/3 HP
motor at 240 volts AC. Kele is a good source for this item at www.Kele.com
.
Refer to the following figure:
Note: You can manually override each output using the Hand-Off-Auto switches as follows:
Hand – Forces output to the ON state
Off – Forces output to the OFF state
Auto – Allows the output to follow the last command from the computer
Installation Guide Page 17 of 20 Copyright 2009
Vista de página 16
1 2 ... 12 13 14 15 16 17 18 19 20

Comentários a estes Manuais

Sem comentários